Plug Fan Heat Recovery Units (Aluminum Heat Exchanger)
FanexIt is manufactured as standard between 500 m³/h and 4,000 m³/h. The outer casing is made of galvanized sheet metal and contains 2 G4 dust filters, 2 plug fans, 1 aluminum plate heat exchanger, and 4 intake and exhaust ports. The filters are on a sliding system. Due to the practicality of our production process, the heat exchanger, plug fans, and filters can be easily removed and installed. The heat recovery unit takes in air, filters it, and returns it to the interior. It takes in fresh air from outside, filters it, heats it, and returns it to the interior. It is used with a heater and control panel.
MODEL | FAN MODEL | VOLTAGE (VOLT/HZ) | MOTOR POWER (WATT) | CURRENT (A) | RPM (d/d) | FLOW RATE (m3/h) | PRESSURE (Pa) | SOUND (dBa) | |
FIGK-P-250 | 220 | 230/50 | 2x105 | 2x0,44 | 2700 | 250 | 150 | 60 | |
FIGK-P-500 | 250 | 230/50 | 2x145 | 2x1,14 | 2650 | 500 | 150 | 60 | |
FIGK-P-750 | 280-02 | 230/50 | 2x420 | 2x1,45 | 2750 | 750 | 150 | 63 | |
FIGK-P-1000 | 315 | 230/50 | 2x135 | 2x0,60 | 1400 | 1000 | 150 | 63 | |
FIGK-P-1500 | 355 | 230/50 | 2x240 | 2x1,1 | 1400 | 1500 | 150 | 56 | |
FIGK-P-2000 | 400 | 230/50 | 2x510 | 2x2,35 | 1400 | 2000 | 150 | 60 | |
FIGK-P-2500 | 400 | 230/50 | 2x510 | 2x2,35 | 1400 | 2500 | 150 | 60 | |
FIGK-P-3000 | 450 | 230/50 | 2x510 | 2x2,35 | 1400 | 3000 | 150 | 58 | |
FIGK-P-3500 | 450 | 230/50 | 2x510 | 2x2,35 | 1400 | 3500 | 150 | 58 | |
FIGK-P-4000 | 450 | 230/50 | 2x510 | 2x2,35 | 1400 | 4000 | 150 | 65 | |
FIGK-P-4500 | 450 | 230/50 | 2x510 | 2x2,35 | 1400 | 4500 | 150 | 65 |